SUMMARY

Periodic storage tank inspection has traditionally meant draining the tank, cleaning it, and sending inspectors into a confined space, an approach that takes the asset out of service and adds safety risk. Structural Integrity Associates (SIA) offers nonintrusive and robotic tank inspection solutions that start with the scope your program actually requires, whether that is an API 653 inspection interval or a nuclear plant license renewal commitment, and then select the least intrusive nondestructive examination (NDE) method that meets it. First developed for nuclear aging management programs, these technologies now support power generation, petrochemical, and municipal utility facilities.

Whenever possible, SIA inspects from outside the tank. Guided Wave Phased Array (GWPA) technology scans the tank floor annulus from the external chime, the zone where corrosion often begins, while the tank stays in service and with minimal surface preparation. On the exterior shell and roof, a remotely operated magnetic crawler climbs carbon steel to perform GWPA screening, phased array ultrasonic testing (PAUT) and time-of-flight diffraction (TOFD) weld examinations, and corrosion mapping along repeatable, programmable scan paths. Pulsed eddy current testing examines insulated structures with little or no insulation removal.

When a full floor examination is needed, SIA’s submersible robotic crawler enters through existing access points, often without draining the tank. GWPA provides 100% volumetric screening to pinpoint areas for follow-up with ultrasonic thickness testing, non-contact EMAT, or SIPEC™, SIA’s proprietary pulsed eddy current technique that reads through internal liners and several inches of sediment. An acoustic positioning system tracks the robot’s location in murky liquid without encoder drift. For remote visual inspection, indoor and submersible inspection drones cover internal surfaces with no personnel entry or scaffolding.

Inspection data is only as useful as the decisions it supports. SIA’s advanced engineering team evaluates findings using finite element analysis and fracture mechanics flaw assessments. For time-critical examinations, engineers can prepare handbooks before the inspection so findings are dispositioned in real time. Results can then feed MAPPro™ for risk ranking and future program planning, and SIA can also assess and modernize aging cathodic protection systems. To see how these capabilities work together, contact SIA to scope your next tank inspection.

Search...